I. Introduction
A pump catalogue may list maximum flow, maximum head, rated flow, rated head, and peak efficiency, but these are not values of a single operating point. If you overlay them as if they occur together, you could recommend the wrong pump and quote performance it can’t deliver. This tutorial shows how to calculate flow and head requirements, read the main curves, find the real duty point and best efficiency point (BEP), and check whether a supplier’s published data may be used.
II. What Do the Lines on a Pump Curve Mean?
1. Head-Flow Curve
The horizontal axis is flow rate, commonly m³/h, L/s, or GPM. The vertical axis represents head, commonly expressed in meters or feet.
The head-flow line usually falls from left to right. A pump produces more head at low flow, but the head drops as the flow rises.
Each spot along this line shows one possible combination of flow and head for the stated speed and impeller diameter.
2. Efficiency Curve
The efficiency curve displays the efficiency of the pump at different flow rates. It can be plotted as a separate line below the head-flow curve or as percentage contours over many of the pump curves.
The BEP sits at the peak of this curve.
Make sure the chart is reporting pump efficiency, pump-and-motor efficiency, or wire-to-water efficiency, as they use different power inputs.
3. Power Curve
The power curve shows the shaft power or input power required at each flow. Read it at the duty point you want to use it at, not just the motor nameplate rating. The motor must be sized for the pump power need over the whole allowable operating range and not just at the BEP.
4. NPSH-Required Curve
The NPSH-required curve shows the suction head the pump requires at each flow rate on its stated basis of test. It doesn’t show what the installation has to offer. It must be compared to the system NPSH available and the required margin applied before approving the pump for the application.
III. How Do You Calculate the Required Flow and Head?
1. Calculate the Required Flow
For a transfer job, take the liquid volume that must be moved and divide it by the pumping time available:
Flow Q = Volume ÷ Time
If a tank must receive 24 m³ of water in two hours, the result is:
Q = 24 ÷ 2 = 12 m³/h
This 12 m³/h is the flow you should mark on the curve. The pump’s published maximum flow is not the system requirement. For a process, irrigation zone, cooling circuit, or multiple outlets, use the design demand for the operating condition instead of calculating from tank volume.
2. Calculate the Required Head
For water moving between two open tanks, use this calculation:
Total head = Static head + Pipe, fitting, and valve losses
If the difference between the two water levels is 18 m and the calculated friction loss at 12 m³/h is 7 m, the pump duty is:
12 m³/h at 25 m head
Friction loss must be calculated at the required flow because it increases as flow rises. Do not add the total pipe length directly to the vertical height; horizontal pipe length affects friction loss, not static head.
3. Add the Required Outlet Pressure
When pressure is still needed at the discharge point, change it to head and include it with the static head and friction loss. For water:
If the system above also requires 1.5 bar at the outlet, add approximately 15.3 m. The revised duty becomes about 12 m³/h at 40.3 m head. For liquids with a different density, use H = Δp ÷ (ρg) rather than the water conversion.
4. Convert Flow Units Correctly
Keep the same unit system from start to finish. For L/s, use the value multiplied by 3.6 to obtain m³/h. For US GPM, use the value multiplied by about 0.227.
A unit error moves the selected point to the wrong part of the curve even when the method is otherwise correct.
IV. How Do You Read the Required Duty Point on the Curve?
1. Confirm the Curve Conditions
Before reading the chart, confirm the pump model, speed, frequency, impeller diameter, test liquid, and units.
If there are many impeller trims or speeds in the catalogue, each one is a separate performance curve.
2. Mark the Required Flow
Locate the desired flow on the horizontal axis and draw a line upward.
Using the earlier example, place your mark at 12 m³/h. Only use the pump’s maximum flow as the starting point when the required flow actually equals it.
3. Find the Intersection with the Head-Flow Curve
Draw an imaginary horizontal line toward the head axis at the intersection of the selected pump curve and the 12 m³/h line.
A 25 m reading means this pump setup reaches the required duty.
If it only reads 20 m, then that setup cannot deliver the required head at 12 m³/h.
When the reading is much higher than 25 m, compare the actual operating point with the system curve. Do not assume that the pump will remain at 12 m³/h.
4. Locate the Actual Operating Point
A centrifugal pump cannot set its flow independently. Its actual operating point occurs where the pump curve meets the system curve.
At zero flow, the system curve begins at the static head. It then rises as flow-related losses increase. A wider valve opening lowers resistance and normally moves the operating point toward higher flow. Throttling has the opposite effect.
5. Read Efficiency, Power, and NPSH at the Same Flow
From the operating point, go straight up to the efficiency, power, and NPSH-required curves.
Read the efficiency, power, and NPSH figures at the same flow.
Total head at the rated point, efficiency at the BEP, and power at maximum flow create a set of figures that the pump never produces at one operating condition.
V. How Do You Find and Check the Best Efficiency Point?
1. Locate the Peak Efficiency
On a separate efficiency line, the BEP is at its highest point. On a contour chart, find the highest efficiency contour crossed by the exact impeller curve.
Use this location to read the flow and head axes, then write down all three items:
– BEP flow
– BEP head
– BEP efficiency
An efficiency percentage without its corresponding flow and head is incomplete.
2. Compare the Required Duty with the BEP
Put the required duty on the chart and check whether it stays within the pump’s preferred operating region around the BEP.
Use the range for that specific pump type and design. Do not use one universal percentage range for all pumps.
Simply appearing somewhere on the head-flow curve does not make a duty point suitable for continuous operation. It still needs to stay within the pump’s allowed operating range.
3. Check the Published Efficiency by Calculation
For a water pump, use the following formula for hydraulic output power:
Hydraulic power (kW) = Q (m³/h) × H (m) ÷ 367
If a pump delivers 50 m³/h at 30 m head, its hydraulic output is approximately:
50 × 30 ÷ 367 = 4.09 kW
If the measured shaft input at that point is 5.5 kW, pump efficiency is:
Efficiency = 4.09 ÷ 5.5 × 100% = 74.4%
Check this number against the published efficiency curve. When electrical input is used instead of shaft input, motor losses become part of the result, so it cannot be compared directly with pump-only efficiency.
VI. Maximum, Rated, and BEP Values: What Is the Difference?
1. Maximum Head
Many sales data sheets show maximum head: the shut-off head at or near zero flow.
Maximum head appears at the far-left side of the curve, where useful flow is normally unavailable.
Some technical standards use the term “maximum allowed head” in a different way, so you should check the supplier’s definition. Never quote maximum head as continuous output without viewing the curve.
For example, a pump with a maximum head of 45 m may produce:
– 45 m at approximately 0 m³/h
– 35 m at 50 m³/h
– 20 m at 100 m³/h
Use the curve for the exact figures.
2. Maximum Flow
The far-right published position, sometimes called pump runout, gives the maximum flow. Head is much lower here than at the maximum-head position.
Operation at this end point may be limited by cavitation, vibration, motor power, or the manufacturer’s range of operation.
Maximum flow and maximum head sit at opposite ends of the curve. Do not treat them as one duty point.
A pump advertised as having a max flow of 120 m³/h and max head of 45 m does not mean it can give 120 m³/h at 45 m.
3. Rated Flow and Rated Head
The rated flow and the rated head describe one specified operating point and have to be always written as a pair, for example:
Rated duty: 12 m³/h at 25 m
Depending on the product and standard, this may be the design point, guaranteed test point, or nominal sales rating.
Rather than relying on two separate figures, ask the supplier to mark the rated point on the curve and state how the rating was set.
4. BEP Flow and BEP Head
The BEP flow and BEP head are the point of best pump efficiency for a given speed and impeller diameter. The rating point is generally picked to be close to the BEP, but they are not always the same.
For example:
– Rated point: 50 m³/h at 32 m
– BEP: 55 m³/h at 30 m
– Maximum flow: 85 m³/h at 15 m
– Maximum head: 42 m at approximately zero flow
These are four different positions on the curve.
VII. How Do You Use the Curve to Compare Pump Models?
1. Reject Impossible Maximum-Value Claims
Suppose a catalogue shows a maximum flow of 120 m³/h and a maximum head of 45 m. Ask for the whole curve. Find the real head at 120 m³/h and the real flow at 45 m.
Without the curve, you cannot see which flow and head the pump can deliver at the same time. Do not join both maximum ratings into one performance claim in your catalogue or quotation.
2. Compare Both Pumps at the Same Duty Point
Assume that Pump A is 82% peak efficient at 100 m³/h, but only 70% efficient at the needed duty of 60 m³/h at 35 m.
Pump B has a lower peak efficiency of 79%, but at the same duty of 60 m³/h at 35 m, it runs at 77%.
For this order, Pump B is the better efficiency match even though its advertised peak efficiency is lower. Looking only at peak figures may lead you to choose the wrong pump.
3. Check the Complete Operating Range
When demand changes, plot the minimum, normal, and maximum duty points rather than looking at only one. Make sure every point stays inside the allowable operating range and still has acceptable motor power and NPSH.
It shows you whether you can do the whole job with one model or if you will need another pump size, impeller diameter, or speed option for your range.
4. Give Each Model a Clear Duty Area
Plot the common flow and head requirements in your market versus the useful operating range for each model. Retain models that cover different jobs and question models whose functional ranges overlap with no clear difference in price, material, control, or application.
Everyone knows what each SKU is for.
This is more dependable when planning a product range than relying on maximum flow and maximum head labels.
VIII. How Do You Verify a Supplier’s Curve?
1. Request Complete and Identified Data
Ask for the following curves, all based on the matching speed and impeller diameter:
– Head versus flow
– Efficiency versus flow
– Power versus flow
– NPSH required versus flow
The document should also identify the test basis, liquid, temperature, units, curve tolerances, and whether power and efficiency refer to the pump or the complete pump unit.
2. Cross-Check the Numbers
Pick one or more positions on the curve. Work out the hydraulic power from the flow and head, and then check it against the published shaft power and efficiency.
For example, if the curve states:
– Flow: 50 m³/h
– Head: 30 m
– Shaft power: 5.5 kW
– Pump efficiency: 85%
The hydraulic power is only 4.09 kW, giving a calculated pump efficiency of approximately 74.4%. The published figures therefore do not agree and require an explanation.
Rounding and test tolerances can cause small differences, but the maths still needs to work and every figure must use the same efficiency boundary.
3. Test the Approved Sample
Before placing a bulk order, test the sample at the rated point and at agreed points on each side.
Record flow, head, speed, power, and efficiency, and check them against the submitted curve under the agreed acceptance standard.
Keep a copy of the approved curve and test results with the order specification. That prevents later production from being tested against a different speed, impeller, motor, or performance curve.
IX. Conclusion
A good pump curve tells you what flow and head go together and what efficiency, power, and NPSH apply at that particular point. Do not combine maximum flow with maximum head. Read all values on curves at the same flow.
Work out the required duty before anything else. Next, look at how the rated point compares with the BEP. The supplier’s figures should also be checked through calculation and sample testing.
For a HunGerät pump selection, send us your needed flow, static height, pipe specifications, outlet pressure, liquid, power supply, and operation pattern.
X. Frequently Asked Questions
1. Which axis shows pump flow?
Flow is normally shown on the horizontal axis in m³/h, L/s, or GPM.
2. Which axis shows pump head?
You will normally find the pump head on the vertical axis, shown in meters or feet.
3. How do you calculate transfer-pump flow?
Use the liquid volume and available transfer time: volume divided by time.
4. How do you calculate total pump head?
Add static head, friction losses, and any pressure head required at the point of discharge.
5. Does horizontal pipe length equal pump head?
No. Horizontal pipe adds friction loss; it is not counted as vertical head.
6. How many metres of water head equal one bar?
For water, 1 bar equals about 10.2 m of head.
7. What is the pump duty point?
It is the required combination of flow and head, e.g. 12 m³/h at 25 m.
8. What determines the actual operating point?
The pump curve and system curve determine it where the two lines meet.
9. What is the BEP?
The BEP marks the flow and head where that pump setup reaches its best efficiency.
10. Is rated flow the same as maximum flow?
No. Rated flow refers to a stated duty point. Maximum flow appears at the far-right limit of the published curve.
11. Is rated head the same as maximum head?
No. Rated head is at rated flow. Maximum head is frequently tested at near zero flow.
12. Can maximum flow and maximum head occur together?
No. They typically occur at opposite ends of a centrifugal pump curve.
13. Can a pump run continuously at shut-off head?
Generally, no. Long periods of no flow might result in fast heating and mechanical damage.
14. Is the rated point always the BEP?
No. It may be near the BEP, but you must check the actual curve.
15. How do you calculate hydraulic power for water?
Multiply Q in m³/h by H in metres, then use that figure divided by about 367.
16. How do you calculate pump efficiency?
Take the hydraulic output power, divide it by the pump shaft input, and express the answer as a percentage.
17. Why can two suppliers show different efficiency values?
The figures can differ because the suppliers may test at different duty points, speeds, impellers, tolerances, or efficiency boundaries.
18. Does reaching the required duty prove the pump is suitable?
No. It still has to meet the pump’s limits for operating range, power, and NPSH.
19. Which curves should you request from a supplier?
Request head-flow, efficiency, power, and NPSH-required curves for the exact pump configuration.